Integra 400 Press Box Specifications

1.1 STRUCTURE

Please provide a ____ (W) x ___(L) x ____ (H) UL Classified prefabricated modular structure for exterior use manufactured by Allied Modular Building Systems, Inc. or equal. Building to be shipped disassembled with all hardware for onsite assembly.

1.2 INSTALLATION

Please provide me with installation, delivery, and pre-wire for the above structure. This includes all travel, installation, labor, and any other expenses that may be incurred to install the walls, doors, ceiling and other non-electrical items.

1.3 PRE-WIRE

Please provide me with all electrical wiring of all outlets, lights, switches, and any other electrical components that are required on this project. All concealed electrical shall be encased in flexible aluminum or steel conduit. All exposed conduit shall be encased in steel conduit. All components shall be wired to a load center /sub panel or one location within the proposed structure. All wiring to the load center / Sub panel shall be wired to breakers that are also provided. All wiring must be field-tested. All wiring shall consist of 12 GA. minimum THHN Type and shall comply with all N.E.C. requirements. All circuits shall be 20 amp single pole or 20 amp 2-pole breakers. A ground wire shall be pulled to all lights, outlets, and any other electrical component. This does not include main electrical hookup or phone and data jacks to the main board.

Note: Modular Wiring is not acceptable.

1.4 FREIGHT

Please provide freight to our facility. Include all freight charges from your facility to ours. Any damages or freight claims shall be filed by the shipper. No additional purchase orders for damaged materials will be accepted. The recipient shall incur no costs for freight claims. This shall include all charges for freight, damage, insurance, fuel surcharges and any other costs that may be incurred. This does not include unloading at the destination facility.

MATERIALS

2.1 WALL PANELS – 4”

The wall shall be 4” actual thickness minimum Combustible or noncombustible. The entire wall system shall be approved by UL (Underwriters Laboratory).

Panels shall be modular and interchangeable with a minimum thickness on 2” overall width. The standard panel shall consist of an insulated rigid polystyrene core permanently laminated between two sheets of noncombustible stucco embossed tempered hardboard. The panels shall be fully fabricated at the factory for easy installation. No splicing shall be necessary for any panels under 10’ total height. All panels will be UL approved and meet a class “A” fire rating which requires a minimum of 0-25 flame spread. The panel types are as follows:

b. Aluminum Embossed Pebble Texture painted skin with a rigid polystyrene foam core..

2.2 BASE CHANNEL

The base channel shall be anodized aluminum or painted aluminum with a minimum thickness of .080. The base channel shall be anchored at 24” O.C. with ½” x 3-1/2” minimum embedded wedge anchor or per engineers specifications. Anchors shall be included with materials.

2.3 POSTS & FRAMING (NON PROGRESSIVE)

Posts shall be anodized aluminum framing channels with minimum temper strength of 6063-T5. The posts will allow a load to 3,500 lbs., but not to exceed 4,000 each and shall be an intricate part of the structure. The channel shall consist of three parts and allow the ability to remove any panel without disturbing adjacent panels. The connecting posts shall serve as an electrical raceway accommodating electrical, data and phone. The raceway shall bear a UL approved sticker and conform to all UL reports.

2.4 WINDOWS-(SINGLE PANE)

Windows shall be installed in panels per customer drawing. Windows shall be of the picture-window type or sliding window type per customer drawing. The window glass shall be a minimum 3/16-inch thick clear, tempered safety glass pre mounted in an aluminum frame. Windows shall be a nominal 40 inches in height and extend across the full width of its supporting panel. The window sill height shall be 41 inches from the floor. The sliding windows shall be able to slide sideways. The sliding windows shall have locks lockable from the inside of the modular office. Weather stripping shall also be provided with the sliding windows.

2.5 PANEL CAPS

Anodized aluminum panel caps or manufacturer’s standard panel caps incorporating a vertical fascia shall be installed securely on the top perimeter of the wall panels. The panel caps shall provide a neat appearance where the wall panels and roof deck come together.

3.0 DOORS

All doors shall be pre-hung at the factory and assembled into panels to ensure easy installation and proper fit. Doors shall be a nominal 36 inches wide by 80 inches high and have thickness of 1-3/4 inches. The interior and exterior finish of the doors shall be color coordinated with the exterior finish of the wall panels. All doors shall have the same finish on both sides. The type of door is as follows:

a. 3068 .18 gauge steel door with standard hinges and Lever hardware.

3.1 SINGLE VISION LITE / WINDOW IN DOOR (Single pane)

The upper half of all doors shall have a 20" x 24" with a minimum 3/16- Inch thick clear tempered safety glass picture window. Rubber shall be placed on the inside of all openings.

4.0 PANELIZED ROOF SYSTEM

The roof system shall be an aluminum roll-formed interlocking panel. The roof deck panels shall be a minimum of .19 gauge thickness with a rigid polystyrene core permanently laminated to aluminum skin. Panels shall be designed to achieve optimum structural efficiency. The Panelized roof shall span the full width of the modular press box and hold a minimum of 30 PSF. live load and 10 PSF. dead load and shall conform to seismic zone 4 requirements. The roof shall be installed with a minimum of 1/4” per ft grade on the overall span.

5.0 HARDWARE

Hardware shall be Allied Modular Standard.

6.0 HEAT / AIR CONDITIONER & OPENING

Appropriate size wall mounted A/C or HVAC shall be provided in accordance with all local mechanical codes. A Heating/Ventilation/Air Conditioner (HVAC) panel shall be located per customer. The HVAC opening shall be of solid construction. The HVAC opening shall reinforced to support a minimum 150 pound wall mounted HVAC unit and shall be lined with aluminum trim. There shall be at least 60 inches between the floor and the bottom of the HVAC opening.

7.0 LIGHT FIXTURES - T8

Light fixtures shall be surface mounted on the ceiling. The light fixtures shall be 2 feet wide by 4 feet long and incorporate T8 4100K lamps with electronic ballasts. Light fixtures shall have a minimum 128-watt capacity and be equipped with diffuser lens. The appropriate quantity of light fixtures shall be located in the ceiling such that a minimum of 50-foot candles lighting at a height of 3 feet from the floor is evenly maintained throughout the modular office. Tubes shall be provided by other.

8.1. LIGHT SWITCHES

A light switch shall be provided at each doorway. Light switches shall be located on the interior wall and opposite the door hinges. Light switches shall be conveniently placed for easy access. Light switches shall be located 42 inches in height from the floor. Light switches shall be provided with cover plates. Light switches shall conform to the National Electric Code.

8.2 ELECTRICAL OUTLETS

Wall outlets shall be standard 110-volt AC duplex outlets. Wall outlets shall be located as shown on drawings. Wall outlets shall be a nominal 18 inches in height from the floor. A 230- volt outlet shall be installed near the HVAC opening at a height of at least sixty inches to interface with the HVAC power cords. Outlets shall be provided with cover plates. Light switches shall conform to the National Electric Code.

OTHER

9.0 FORKLIFTABLE STEEL BASE

A forklift able steel base shall be constructed of heavy duty steel C-channel with appropriate size supports to handle building size. The base shall be equipped with forklift sleeves to enable the lifting of the entire completed unit. The top of the base shall be 1-1/8” T&G Plywood. Floor tile is optional.

10.0 WARRANTY

All workmanship shall be guaranteed to be free of defects for a period of one year from the date of shipment. All materials to be free of manufacturers defect for ten years from the date of shipment. For items not manufactured by Allied Modular, the manufacturers warranty applies. Installation is not covered under warranty unless provided by Allied Modular's factory trained installers.